Related posts
Feature
1. Global universal full range AC input voltageNatural ventilation cooling 100% full load aging test2. Installed on the DIN guide TS35/7.5 or 15Applicable to the field of building automation and control
3. Short circuit protection / overload protection / overvoltage protectionClassII insulation level
4. The use of lead-free process is in conformity with the requirements of environmental protection RoHS
5. 2 year warranty International safety regulations UL/CUL/TUV/CB/CE
Description
DC output range: 24V, 01.5A
Output voltage accuracy: 1%
Ripple: 150mV
Efficiency: 83%
Input voltage range: 85264VAC/120370VDC
Input surge current: cold start 65A/230V
Voltage adjustment range: +10% rated output voltage
Overload protection: over current point at 105%160% constant current limit current automatic recovery.
Overvoltage protection: the rated output voltage is 115% to 135% off when zener diode clamping.
Start up hold time: 230VAC full load 1000ms, 50ms, 70ms
Insulation characteristics: between the input and the output: 3KVac
Working temperature: -20+60 C (see output load drop curve)
Aseismic mobility: 10500Hz, 2G 10 minutes / cycle, XYZ axis 60 minutes each.
Safety certification: through UL60950-1, TUV60950-1 certification, according to EN50178 design.
EMC standards: Launch: EN55011, EN55022 (CISPR22), EN61204-3 class B, harmonics: EN61000-3-2, -3
EMC standards: anti jamming: EN61000-4-2,3,4,5,6,8,11, ENV50204, ENV55024, EN61000-6-2, EN61204-3, A-level heavy industry standard.
The mean time to failure is more than 1 million 172 thousand and 300 hours, MIL-HDBK-217F (25 C).
Connection mode: input port: 3 point. Output: 2 point screw DIN terminal
Shape size: 78*93*56mm (Wide x High x Depth)
Weight: 0.27kg